Starting watts vs running watts
Generators this size are home standby units, sold by their running rating in kilowatts on propane — on natural gas, the 2 models this size that list both figures deliver about 92% of it. Their makers publish motor-starting capability in kVA rather than starting watts, and Briggs & Stratton state their units start a 5-ton central AC. Like the calculator, we count on starting power of about a quarter above the rating — the short burst a motor needs to start[1] — which is about 37,500 W for a 30,000-watt unit.
For loads that run for hours, stay under about 80% of the running rating — about 24,000 W — so the generator isn’t working flat out. Check each appliance’s label for its watts; if it lists only amps, multiply by the voltage.[2]
Will a 30,000-watt generator run central air?
Yes. Central AC (3 ton) needs about 3,500 W running and 10,500 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Will a 30,000-watt generator run a heat pump?
Yes. Heat pump needs about 4,700 W running and 9,200 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Will a 30,000-watt generator run an electric water heater?
Yes. Electric water heater needs about 3,900 W running, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Will a 30,000-watt generator run a well pump?
Yes. Well pump (1/2 HP) needs about 1,000 W running and 2,550 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Bigger unit: Well pump (1 HP) needs about 2,000 W running and 6,000 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Will a 30,000-watt generator run an electric dryer?
Yes. Electric dryer needs about 5,500 W running and 6,400 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
What a 30,000-watt generator runs, appliance by appliance
Each appliance on its own, with the typical running and starting watts the calculator uses. Start one motor at a time, and add up everything else that’s running.
| Appliance | Running | Starting | On a 30,000-watt generator |
|---|---|---|---|
| Kitchen | |||
| Refrigerator | 700 W | 2,900 W | Runs it |
| Chest freezer | 500 W | 1,500 W | Runs it |
| Upright freezer | 700 W | 2,900 W | Runs it |
| Microwave (1,000 W) | 1,000 W | 1,000 W | Runs it |
| Coffee maker | 1,300 W | 1,300 W | Runs it |
| Toaster | 1,100 W | 1,100 W | Runs it |
| Slow cooker | 250 W | 250 W | Runs it |
| Dishwasher | 1,500 W | 1,500 W | Runs it |
| Electric stove, 8-inch burner | 2,100 W | 2,100 W | Runs it |
| Heating & Cooling | |||
| Furnace fan (1/2 HP) | 875 W | 3,150 W | Runs it |
| Furnace fan (1/3 HP) | 700 W | 2,100 W | Runs it |
| Window AC (10,000 BTU) | 1,200 W | 2,200 W | Runs it |
| Window AC (12,000 BTU) | 1,700 W | 4,200 W | Runs it |
| Central AC (3 ton) | 3,500 W | 10,500 W | Runs it |
| Heat pump | 4,700 W | 9,200 W | Runs it |
| Space heater | 1,500 W | 1,500 W | Runs it |
| Dehumidifier | 650 W | 1,950 W | Runs it |
| Box fan | 150 W | 300 W | Runs it |
| Ceiling fan | 75 W | 75 W | Runs it |
| Water | |||
| Sump pump (1/2 HP) | 1,050 W | 2,700 W | Runs it |
| Sump pump (1/3 HP) | 800 W | 2,100 W | Runs it |
| Sump pump (3/4 HP) | 1,200 W | 3,600 W | Runs it |
| Well pump (1/2 HP) | 1,000 W | 2,550 W | Runs it |
| Well pump (1 HP) | 2,000 W | 6,000 W | Runs it |
| Electric water heater | 3,900 W | 3,900 W | Runs it |
| Laundry | |||
| Washing machine | 1,150 W | 2,800 W | Runs it |
| Electric dryer | 5,500 W | 6,400 W | Runs it |
| Gas dryer | 700 W | 2,100 W | Runs it |
| Everyday | |||
| LED lights (10 bulbs) | 100 W | 100 W | Runs it |
| TV (LED 55") | 150 W | 150 W | Runs it |
| Wi-Fi router + modem | 20 W | 20 W | Runs it |
| Laptop | 150 W | 150 W | Runs it |
| Desktop computer + monitor | 800 W | 800 W | Runs it |
| Phone chargers | 25 W | 25 W | Runs it |
| Security system | 100 W | 100 W | Runs it |
| Hair dryer | 1,500 W | 1,550 W | Runs it |
| Garage door opener (1/2 HP) | 700 W | 1,450 W | Runs it |
| Medical | |||
| CPAP (with heated humidifier) | 120 W | 120 W | Runs it |
| Oxygen concentrator (5 LPM) | 350 W | 1,050 W | Runs it |
Running several things at once
Everything running together has to stay under about 30,000 W with headroom, and the biggest startup has to fit within 37,500 W. Motors don’t start in the same second, so only the largest jump counts.
- The whole-house list with a second central ACFits: about 16,670 W running and 23,670 W at startup.
- All-electric house: heat pump, water heater, dryer and stove all at onceFits: about 21,095 W running and 25,595 W at startup.
- All-electric house plus two central AC unitsToo much: about 28,095 W running and 35,095 W at startup.
30,000-Watt generators in our database
The models in our database rated 26,000 W to 32,000 W running, which this page’s numbers come from. Specs are from each maker’s official page; the model names link to them. See all generators by size.
| Model | Running | Starting |
|---|---|---|
| Generac · Home standby · Natural gas / LPGuardian 26kW (G0073270) | 26,000 W | not published |
| Briggs & Stratton · Home standby · Natural gas / LP · Starts a 5-ton ACPowerProtect+ 26kW (040807) | 26,000 W | 65.5 kVA motor start |
| Generac · Home standby · Natural gas / LP30kW liquid-cooled (RG03015A) | 30,000 W | not published |
| Generac · Home standby · Natural gas / LPXG Protector 32kW, 120/240 V (XG03245ANAX) | 32,000 W | not published |
Before you plug in
Use an electrician
Transfer switches and interlocks are installed by a qualified electrician.[6]
Questions
Is 30,000-watt the running or the starting rating?
The running rating. Home standby generators are sold by their continuous kilowatts on propane — 30 kW is 30,000 W — and deliver a little less on natural gas, about 27,650 W.
Will a 30,000-watt generator run central air?
Yes. Central AC (3 ton) needs about 3,500 W running and 10,500 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Will a 30,000-watt generator run a heat pump?
Yes. Heat pump needs about 4,700 W running and 9,200 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Will a 30,000-watt generator run an electric water heater?
Yes. Electric water heater needs about 3,900 W running, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Will a 30,000-watt generator run a well pump?
Yes. Well pump (1/2 HP) needs about 1,000 W running and 2,550 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
Will a 30,000-watt generator run an electric dryer?
Yes. Electric dryer needs about 5,500 W running and 6,400 W for a second to start, within a 30,000-watt generator. It runs through the generator’s automatic transfer switch.
How is a 30,000-watt generator connected to the house?
A home standby generator is installed permanently outside and wired to your panel through an automatic transfer switch by a licensed electrician, with a licensed plumber or gas fitter for the gas line. Most areas require a permit.[6]